Theory: The Rankine Steam Cycle
Why the Steam Cycle Matters
A nuclear plant is a heat engine. The reactor supplies heat, but only about a third of it becomes electricity; the rest must be rejected to a river, lake, sea, or cooling tower. The secondary-side performance engineer tracks turbine efficiency, condenser vacuum, and heat rate every day, because each 0.1% of efficiency is worth over a megawatt of output for the life of the plant. The same thermodynamics sets the size of the cooling system and the plant's environmental permits.
The Rankine Cycle
Water and steam pass through four steps. (1→2) Saturated steam from the steam generator expands through the turbine to the condenser pressure, producing work. (2→3) The wet exhaust steam condenses to saturated liquid in the condenser. (3→4) The feed pump raises the liquid back to steam-generator pressure. (4→1) The steam generator boils it again. An ideal turbine expands steam isentropically (at constant entropy); a real turbine reaches a higher exhaust enthalpy, described by its isentropic efficiency.
Real exhaust: h₂ = h₁ − η_t (h₁ − h₂s)
Net work: w_net = (h₁ − h₂) − w_p Heat added: q_in = h₁ − h₄
η = w_net / q_in
Electrical Output, Heat Rejection, and Heat Rate
The plant's electrical output is the reactor power times the cycle efficiency and the generator efficiency. Almost all the remaining heat leaves through the condenser, where cooling water carries it away. The heat rate (heat input per kilowatt-hour of electricity) is the industry's standard measure of plant performance; lower is better.
Cooling water: ṁ = Q_rej / (c_p ΔT) Heat rate = 3600 / (η η_gen) kJ/kWh
Reading the Cycle on a T–s Diagram
On a temperature–entropy diagram, heat added in a reversible process is the area under its path, so the cycle's net work is the area enclosed. An ideal turbine expands straight down at constant entropy (1 → 2s); a real turbine generates entropy, so state 2 lies to the right and the lost work is about T_cond × (s₂ − s₁). The mean temperature of heat addition, T̄ = (h₁ − h₄)/(s₁ − s₄), sets the best efficiency possible, 1 − T_cond/T̄. Raising the condenser temperature in summer raises T_cond and lowers both the ideal limit and the real output.
T̄ = (h₁ − h₄)/(s₁ − s₄) · η_ideal ≤ 1 − T_cond/T̄
Steam-Table Data Used in This Lab
| State | T_sat (°C) | h_f | h_fg | s_f | s_fg | v_f (m³/kg) |
|---|---|---|---|---|---|---|
| Throttle: 6.9 MPa saturated steam | 285 | h₁ = h_g = 2773 kJ/kg | s₁ = s_g = 5.815 kJ/kg·K | — | ||
| Condenser 5 kPa | 32.9 | 137.8 | 2423.0 | 0.4763 | 7.9187 | 0.001005 |
| Condenser 7 kPa | 39.0 | 163.4 | 2409.1 | 0.5591 | 7.7167 | 0.001007 |
| Condenser 10 kPa | 45.8 | 191.8 | 2392.8 | 0.6493 | 7.5009 | 0.001010 |
Properties from standard steam tables, rounded (enthalpy in kJ/kg, entropy in kJ/kg·K), as used in the DOE Fundamentals Handbook (Thermodynamics, Heat Transfer, and Fluid Flow). Real plants reach 33–35% with moisture separators, reheaters, and feedwater heaters, which this simple cycle leaves out.
Performance engineering
Engineers trend turbine efficiency, condenser vacuum, and heat rate to find losses worth fixing.
Environmental permits
Cooling-water flow and temperature rise are limited by discharge permits that protect rivers and lakes.
Uprates
Power uprates and turbine retrofits are justified by the extra megawatts calculated from these balances.
Apparatus
The secondary-plant equipment of a nuclear unit. In the simulation these are modelled for you, and the readings correspond to what each would show.
Instructions: Running the Virtual Experiment
You are the performance engineer for the secondary plant. The simulation has two immersive 3D work areas and two graph work areas. The parts build from undergraduate work in Parts A and B to graduate-level analysis in the last step of Parts C and D; the level of each part is shown beside its title. In each one you set the conditions, work out the answer yourself, enter it, and press Check. Record every reading and calculation in your lab report tables (modelled in the Example Report), with a labelled screenshot of each setup. Drag in any 3D view to orbit, and scroll to zoom. Each graph also lists its plotted values in a table you can open below it. Use the steam-table data in the Theory section.
Simulation: Turbine Expansion, Condenser Heat Balance, and Performance Graphs
Saturated steam at 6.9 MPa enters the turbine (state 1) and expands to the condenser pressure (state 2). Condensate leaves the condenser as saturated liquid (state 3), and the feed pump raises it back to 6.9 MPa (state 4). Part A uses this work area.
Setup
Readings
Pump work w_p = v_f (P_high − P_low) in kJ/kg (with pressures in kPa). Thermal efficiency = net work / heat added.
Work it out, then check
| P_cond (kPa) | η_t | x₂s | h₂s (kJ/kg) | h₂ (kJ/kg) | w_p (kJ/kg) | w_net (kJ/kg) | η (%) |
|---|
Only about a third of the reactor's heat becomes electricity. The rest is rejected in the condenser and carried away by circulating cooling water. Part B uses this work area.
Setup
Readings
Electrical output = P_th × η × η_gen. Heat rejected in the condenser ≈ P_th (1 − η). Heat rate = 3600 / (η × η_gen) kJ per kWh.
Work it out, then check
| P_th (MW) | η (%) | ΔT (°C) | MWe | Q_rej (MW) | Cooling water (m³/s) | Heat rate (kJ/kWh) |
|---|
A temperature–entropy diagram shows the whole cycle at once. The area under the heating line is the heat added; a real turbine moves state 2 to the right of the ideal state 2s. Part C uses this work area.
Setup
Readings
x₂ = (h₂ − h_f)/h_fg; s₂ = s_f + x₂ s_fg. Mean temperature of heat addition T̄ = (h₁ − h₄)/(s₁ − s₄), with s₄ ≈ s_f.
Work it out, then check
| P_cond (kPa) | η_t | T_sat (°C) | x₂s | x₂ | s₂ − s₁ (kJ/kg·K) | T̄ (K) |
|---|
Condenser pressure is set by the cooling-water temperature. A few kilopascals of lost vacuum cost many megawatts. Part D uses this work area.
Setup
Readings
MWe = 3411 × η × 0.985. Heat rate = 3600/(η × 0.985) kJ/kWh. Compare each pressure with the 5 kPa winter case.
Work it out, then check
| P_cond (kPa) | η_t | η (%) | MWe | MW lost vs 5 kPa | Heat rate (kJ/kWh) | Heat-rate rise (kJ/kWh) |
|---|
This accessible version provides the same set-up, work-out, and check exercises as the 3D and graph work areas, using native controls, data tables, and screen-reader announcements.
Team Questions
Example Lab Report
Sample report showing the expected format and level of detail. Use it as a guide for your own submission, and include labelled screenshots of each setup.
The Steam Cycle: Turbine, Condenser, and Plant Efficiency
Nuclear Engineering Technology | Section: [Your Section] | Date: [Date]
Lab Members: [Names of all members present]
Purpose
To calculate the state points, net work, and thermal efficiency of a nuclear plant's Rankine cycle for different condenser pressures and turbine efficiencies, and the electrical output, heat rejection, cooling-water flow, and heat rate of the plant; and to use a temperature–entropy diagram and a graph of output against condenser pressure to locate where the cycle loses work.
Theory
The turbine expands steam from h₁ to h₂ = h₁ − η_t(h₁ − h₂s), where h₂s follows from constant entropy. Net work is (h₁ − h₂) − w_p and efficiency is w_net/(h₁ − h₄). Output is P_thηη_gen, and the condenser rejects about P_th(1 − η).
Table A: Rankine Cycle Undergraduate
| P_cond (kPa) | η_t | x₂s | h₂s | h₂ | w_p | w_net | η (%) |
|---|---|---|---|---|---|---|---|
| 7 | 0.85 | 0.6811 | 1804.3 | 1949.6 | 6.94 | 816.5 | 31.37 |
| 7 | 0.90 | 0.6811 | 1804.3 | 1901.1 | 6.94 | 864.9 | 33.23 |
| 5 | 0.85 | 0.6742 | 1771.4 | 1921.6 | 6.93 | 844.5 | 32.13 |
| 10 | 0.85 | 0.6887 | 1839.7 | 1979.7 | 6.96 | 786.4 | 30.55 |
Units: enthalpies and work in kJ/kg. Sample calculation (7 kPa, 0.85): x₂s = (5.815 − 0.5591)/7.7167 = 0.6811; h₂s = 163.4 + 0.6811 × 2409.1 = 1804.3; h₂ = 2773 − 0.85 × 968.7 = 1949.6; w_p = 0.001007 × 6893 = 6.94; η = 816.5/2602.7 = 31.37%.
Table B: Plant Output and Cooling Undergraduate
| P_th (MW) | η (%) | ΔT (°C) | MWe | Q_rej (MW) | Cooling water (m³/s) | Heat rate (kJ/kWh) |
|---|---|---|---|---|---|---|
| 3411 | 31.37 | 10 | 1054 | 2341 | 56.0 | 11 651 |
| 3411 | 33.23 | 10 | 1116 | 2278 | 54.5 | 10 999 |
| 3411 | 34.04 | 10 | 1144 | 2250 | 53.8 | 10 737 |
| 3411 | 31.37 | 6 | 1054 | 2341 | 93.3 | 11 651 |
| 2558 | 31.37 | 10 | 790 | 1756 | 42.0 | 11 651 |
Table C: The Cycle on a T–s Diagram Upper undergraduateGraduate step
| P_cond (kPa) | η_t | T_sat (°C) | x₂s | x₂ | s₂ − s₁ (kJ/kg·K) | T̄ (K) |
|---|---|---|---|---|---|---|
| 7 | 0.85 | 39.0 | 0.6811 | 0.7414 | 0.4655 | 495.2 |
| 7 | 1.00 | 39.0 | 0.6811 | 0.6811 | 0.0000 | 495.2 |
| 7 | 0.75 | 39.0 | 0.6811 | 0.7816 | 0.7758 | 495.2 |
| 5 | 0.85 | 32.9 | 0.6742 | 0.7362 | 0.4910 | 492.3 |
| 10 | 0.85 | 45.8 | 0.6887 | 0.7472 | 0.4389 | 498.3 |
| 20 | 0.85 | 60.06 | 0.7043 | 0.7591 | 0.3877 | 504.6 |
Sample calculation (7 kPa, 0.85): x₂ = (1949.6 − 163.4)/2409.1 = 0.7414; s₂ = 0.5591 + 0.7414 × 7.7167 = 6.2805, so s₂ − s₁ = 0.4655; T̄ = (2773 − 170.3)/(5.815 − 0.5591) = 495.2 K. Include a screenshot of the diagram.
Graduate step: at 7 kPa, 1 − T_cond/T̄ = 1 − 312.15/495.2 = 36.96%. η_II = 31.37/36.96 = 84.9% at η_t = 0.85, 100.0% at η_t = 1.00, and 74.8% at η_t = 0.75 (84.9% at 5, 10, and 20 kPa with η_t = 0.85).
Table D: Output against Condenser Pressure (3411 MWt, η_t = 0.85) Upper undergraduateGraduate step
| P_cond (kPa) | η_t | η (%) | MWe | MW lost vs 5 kPa | Heat rate (kJ/kWh) | Heat-rate rise (kJ/kWh) |
|---|---|---|---|---|---|---|
| 4 | 0.85 | 32.60 | 1095 | −16 | 11211 | −164 |
| 5 | 0.85 | 32.13 | 1080 | 0 | 11375 | 0 |
| 7 | 0.85 | 31.37 | 1054 | 25 | 11650 | 275 |
| 10 | 0.85 | 30.55 | 1026 | 53 | 11964 | 589 |
| 15 | 0.85 | 29.57 | 993 | 86 | 12360 | 985 |
| 20 | 0.85 | 28.83 | 969 | 111 | 12676 | 1301 |
MWe = 3411 × η × 0.985; heat rate = 3600/(η × 0.985). Negative values at 4 kPa are gains over the winter case. Include a screenshot of the graph.
Graduate step: with 25 °C inlet water, T_sat = 25 + 10 + 5 = 40 °C, so ln P interpolation gives P_cond = 7.38 kPa. The output is 1050 MWe at η_t = 0.85 (30 MWe below the 5 kPa winter case) and 1112 MWe at η_t = 0.90.
Discussion
The turbine exhaust was only 68% vapour, which is why real plants add moisture separators to protect the low-pressure blades. Improving the turbine from 0.85 to 0.90 raised the efficiency by 1.9 points and the output by 62 MWe. Lowering the condenser pressure from 10 to 5 kPa, which needs colder cooling water, raised the efficiency by 1.6 points, which is why plants make more power in winter. The pump work was under 1% of the turbine work.
At 31.4% efficiency the plant rejected 2341 MW, more than twice its electrical output, and needed 56 m³/s of cooling water for a 10 °C rise. A permit that limits the rise to 6 °C raises the flow to 93 m³/s. The heat rate of 11 650 kJ/kWh fell to 10 740 kJ/kWh at 34% efficiency. Heat rate does not depend on power level in this simple model, though real plants are least efficient at low load.
The graphs showed where the losses come from. On the T–s diagram, a less efficient turbine moved state 2 to the right: the exhaust got drier (x₂ = 0.7414 against x₂s = 0.6811 at η_t = 0.85), but 0.4655 kJ/kg·K of entropy was generated, and T_condΔs ≈ 312 × 0.4655 ≈ 145 kJ/kg of work was lost. The mean temperature of heat addition was only about 495 K because the feedwater is heated from condenser temperature, so even an ideal cycle between 495 K and 312 K could reach only 1 − 312/495 = 37%. The second graph showed output falling steadily with condenser pressure: about 53 MWe is lost between a winter 5 kPa and a summer 10 kPa, roughly 10 MWe per kilopascal in that range, and running at 20 kPa costs 111 MWe. This is why condenser cleanliness and air in-leakage are watched every shift.
The graduate steps tied the two graphs to second-law analysis and design. Once feedwater heating is counted through T̄, the cycle reached about 85% of the best reversible cycle between T̄ and the condenser at η_t = 0.85, and η_II rose to 100% with an ideal turbine, so nearly all of the remaining second-law loss is in the turbine. The summer design case showed how the cooling-water temperature, its rise, and the condenser terminal difference set the vacuum: 25 °C water gave 7.38 kPa and cost 30 MWe against winter, and every degree of extra inlet temperature costs output in the same way.
Conclusion
Steam-table calculations gave a Rankine efficiency of 30.5 to 33.2%, rising with turbine efficiency and condenser vacuum. Two-thirds of the reactor heat is rejected in the condenser, setting the size of the cooling system.
Practice Questions
Show all work and include units. Use the steam-table data in the Theory section.